Furnace Safety Supervision System

1.System Overview

Boiler Furnace Safety Monitoring System, or FSSS (Furnace Safeguard Supervisory System), is to ensure the safe operation of boiler-critical systems, which started in the boiler, and stop running all stages of continuous monitoring of the boiler operating parameters, in accordance with provisions of Ex order security conditions, continually carry out logic judgment and calculation, the corresponding interlock device through the combustion facilities in accordance with established procedures to complete the necessary operations to avoid explosive air - in the fuel mixture accumulated inside the furnace and flue, and boiler in the event of endangering the safety of working conditions , entered the chamber quickly cut off all fuel to prevent the occurrence of explosion of a furnace.

 

2.Block diagram of a system

Furnace Safety Monitoring System (FSSS) mainly by the operating station, operation panels, the main control cabinet, ignition control system, flame detector and cooling air system, and other components. Including the fuel system, throttle bodies monitoring the implementation, chamber pressure, drum level, the blower fan which, by the door, and other signal conditioning warm water monitoring, as well as with DCS communications. System structure indicative figure:

 

3 Main function of the system

-Main fuel tripping MFT (Main Fuel Trip)

-Fuel oil Trip OFT

-Oil leak test system

-Furnace Purge

-Oil combustion system management (signal detection and control)

-Pulverized coal combustion system management (signal detection and control)

-Rapid load-shedding Fast Cut Back

-By load Run Back

-Signal detection and extinguishing the flame protection

-Alarm and display (node failure, the furnace pressure drum water level alarm limits,  combustion instability alarm.)

-Flame detector cooling wind management

-And DCS Communications

-Controlled ignition (Local / Remote)

-MFT first memory of the accident, analysis shows

-Accident causes chronicles functional movements

-Recollections functional simulation curve

 

4 .FSSS system workstations main technical parameters

-Analog sampling resolution1 / 4096

-Analog sampling period20ms/16 channel
-Witching response time
less than 3 ms
-MFT output Contact capacity
10 A/220V AC
-Logic signal output tap capacity
0.5 A/24V DC
-Work Power
AC 220V ± 10% 50Hz
-Ambient temperature
0 ~ 50 ° C
-Environment humidity
10 to 90% RH
-Rack size
standard or user-defined

 

5.system configuration

Typical boiler system configuration

 

Supporting users to provide the following equipment:

1).FSSS workstations, and communication interfaces Annex
2). Logic control the cabinets

3).Auxiliary cabinets and I / O Interface
4).Power counters

5).Operating panels
6). Flame detector, Signal Processor and specific cables

7). Flame detector cabinet
8). Flame detector cooling air system: centrifugal fan of cold air, switch plate, inlet screen, on-site control cabinet of cold air, Wind pressure switch
9).Fuel systems: fuel pressure switch, the fuel pressure switch, fuel temperature switch, the mother of oil jumped valve, the valve such as recycling
10). Pressure switches for boiler: High boiler furnace pressure switch, Low boiler furnace pressure switch, High boiler furnace pressure switch alarm, low boiler furnace pressure switch alarm.

11). Communication interface and cable